Inhibited and Uninhibited Transformer Oils

Inhibited and Uninhibited Transformer Oils: What’s the Difference?

The primary distinction between inhibited and uninhibited transformer oils lies in their chemical composition and oxidative stability. Inhibited transformer oil contains specific chemical additives, called oxidation inhibitors, designed to slow the degradation process, significantly enhancing the oil’s lifespan and performance under demanding conditions. In contrast, uninhibited transformer oil lacks these stabilizing additives, making it more susceptible to oxidation and degradation over time. These differences strongly affect the selection of oil applicable to an application, maintaining needs, operating efficiency, and life cycle cost.

For advanced maintenance and optimization solutions, explore INVEXOIL’s Transformer Oil Purification Machine and Transformer Oil Regeneration Services based on IEC 60296 & IEC 60422 standards.

Characteristics of Inhibited and Uninhibited Transformer Oils

Transformer oil stability, efficiency, and maintenance demands are significantly influenced by the presence or absence of oxidation inhibitors.

Inhibited Transformer Oils

Inhibited transformer oils are formulated with oxidation inhibitors, typically phenolic compounds like 2,6-di-tert-butyl-para-cresol (DBPC) or aminic compounds. These additives act as sacrificial agents, neutralizing free radicals that accelerate oxidation reactions. The benefits are multifaceted:

Enhanced Stability: By slowing oxidation, these oils maintain their chemical integrity longer, minimizing the formation of sludge and acidic byproducts.

Prolonged Service Life: With reduced oxidation degradation, inhibited oils require less frequent replacement, lowering lifecycle costs.

Thermal Efficiency: Improved thermal stability supports consistent performance in high-load, high-temperature environments.

Table 1: Inhibited Transformer Oil Specifications

Property Units Specification Test Method Remarks
Appearance Clear, free from sediments Visual Inspection No haziness, particles, or suspended matter
Density at 20°C kg/m³ ≤ 895 ISO 3675 / ASTM D1298 Lower density preferred for reduced weight on windings
Kinematic Viscosity at 40°C mm²/s (cSt) ≤ 12.0 ISO 3104 / ASTM D445 Ensures fluidity and heat dissipation
Pour Point °C ≤ -40 ISO 3016 / ASTM D97 Suitable for cold climates
Flash Point °C ≥ 135 ISO 2719 / ASTM D93 Indicates safety in terms of flammability
Interfacial Tension (IFT) at 25°C mN/m ≥ 40 ISO 6295 / ASTM D971 Measures contamination; higher values indicate purer oil
Neutralization Number (Acidity) mg KOH/g ≤ 0.03 IEC 62021 / ASTM D974 Acid content, linked to oil degradation
Corrosive Sulfur Non-corrosive IEC 62535 Ensures compatibility with copper and other metals
Dielectric Breakdown Voltage (DGA treated) kV ≥ 70 IEC 60156 Ensures excellent insulating properties
Water Content ppm ≤ 30 IEC 60814 Lower moisture levels improve dielectric strength
Oxidation Stability at 120°C (164 hours) IEC 61125 Method C Measures aging characteristics
– Total Acidity mg KOH/g ≤ 1.2 Limit on degradation products
– Sludge % weight ≤ 0.8 Sludge formation indicates degradation
Inhibitor Content % by weight 0.08–0.4 IEC 60666 Inhibited oils have antioxidants to improve stability
Particle Count particles/mL ≤ 500 (per IEC table) ISO 4406 Cleanliness critical for modern high-voltage equipment
PCB Content ppm Non-detectable (<2 ppm) IEC 61619 / ASTM D4059 Mandatory environmental safety regulation

 

Uninhibited Transformer Oils

Uninhibited Transformer Oils, by contrast, rely solely on their intrinsic stability, which is typically lower than their inhibited counterparts. The absence of additives means these oils degrade faster when exposed to oxygen, heat, and electrical stress. This degradation leads to the formation of sludge and acids that can impair transformer performance and shorten its lifespan. Although uninhibited oils are simpler and cheaper initially, they often demand higher maintenance costs over time.

Table 2: Uninhibited Transformer Oil Specifications

Property Units Specification Test Method Remarks
Appearance Clear, free from sediments Visual Inspection No haziness, particles, or suspended matter
Density at 20°C kg/m³ ≤ 895 ISO 3675 / ASTM D1298 Lower density preferred for reduced weight on windings
Kinematic Viscosity at 40°C mm²/s (cSt) ≤ 12.0 ISO 3104 / ASTM D445 Similar flow characteristics as inhibited oil
Pour Point °C ≤ -40 ISO 3016 / ASTM D97 Suitable for cold climates
Flash Point °C ≥ 135 ISO 2719 / ASTM D93 Indicates safety in terms of flammability
Interfacial Tension (IFT) at 25°C mN/m ≥ 40 ISO 6295 / ASTM D971 Measures contamination; higher values indicate purer oil
Neutralization Number (Acidity) mg KOH/g ≤ 0.03 IEC 62021 / ASTM D974 Acid content, linked to oil degradation
Corrosive Sulfur Non-corrosive IEC 62535 Ensures compatibility with copper and other metals
Dielectric Breakdown Voltage (DGA treated) kV ≥ 70 IEC 60156 Ensures excellent insulating properties
Water Content ppm ≤ 30 IEC 60814 Lower moisture levels improve dielectric strength
Oxidation Stability at 120°C (164 hours) IEC 61125 Method C Less stable compared to inhibited oil
Total Acidity mg KOH/g ≤ 0.3 Higher limit compared to inhibited oil
Sludge % weight ≤ 0.05 Minimal sludge formation due to lack of inhibitors
Inhibitor Content % by weight Not added IEC 60666 Uninhibited oils rely on inherent stability of base oil
Particle Count particles/mL ≤ 500 (per IEC table) ISO 4406 Cleanliness critical for modern high-voltage equipment
PCB Content ppm Non-detectable (<2 ppm) IEC 61619 / ASTM D4059 Mandatory environmental safety regulation

 

Key Differences of Inhibited and Uninhibited Transformer Oil Specifications:

The main differences between inhibited and uninhibited transformer oils are oxidative stability, sludge formation, and the presence of additives. Inhibited oils include, among others, 0.08-0.4% weight antioxidant additives, DBPC or BHT. These additives improve oxidation resistance and provide long service performance with reduced sludge formation under high temperatures and for extended service life. By contrast, uninhibited oils depend entirely upon the inherent stability of their base oil and are thus more susceptible to oxidation and the resulting sludge.

This is reflected in the more severe sludge and total acidity limits for inhibited oils following aging tests. While both oils have similar basic physical and electrical properties, such as dielectric strength, water content, and interfacial tension, the presence of inhibitors in the inhibited oil makes it perform better in highly thermal and oxidative stressed applications. Normally, uninhibited oils are selected for systems with operational conditions that are less harsh or have specific environmental considerations.

Table 3: Comparison of Inhibited and Uninhibited Transformer Oils

Property Inhibited Transformer Oils Uninhibited Transformer Oils
Oxidation Resistance High due to chemical inhibitors Low, prone to sludge and acid formation
Lifespan Longer, reducing maintenance needs Shorter, requires frequent replacement
Applications High-voltage and critical systems Low-voltage or less critical systems
Cost Higher due to additives Lower, but higher long-term costs

 

Application of Inhibited Transformer Oils

Inhibited transformer oils are ideal for high-voltage systems and environments subjected to thermal and electrical stress. Their use is prevalent in critical infrastructure, such as power transmission networks, industrial transformers, and high-capacity substations. The stability provided by inhibitors ensures consistent performance over extended intervals, reducing operational risks and downtime.

Application of Uninhibited Transformer Oils

Uninhibited oils are better suited for low-voltage transformers in residential or commercial setups, where operational demands are modest, and maintenance intervals are more flexible. These oils are also preferred in certain regions or systems where regulatory or environmental considerations favor simpler formulations.

Inhibited and Uninhibited Transformer Oils
INVEXOIL’s Transformer Oil Purification Machine

Key Considerations for Selection

The selection of transformer oil is deeply contextual and influenced by operational conditions, system design, and maintenance strategies. The choice between inhibited and uninhibited oils requires careful evaluation of several factors:

Environmental Conditions: Under higher-temperature or high-humidity conditions, inhibited oils are superior because they do not easily deteriorate.

Voltage Levels and Load Cycles: High-voltage systems benefit significantly from the stability of inhibited oils, while uninhibited oils may suffice for lower-voltage applications.

Maintenance Practices: When systems are under strict conditions of maintenance, they can offset the negative effects of using uninhibited oils, and thus, when upfront cost savings are a bigger issue, those systems may elect to take advantage of such options.

Regular monitoring and analysis of oil properties, including dielectric strength, moisture content, and acid number, are essential for ensuring optimal performance, regardless of the oil type.

Related Artcile: Understanding Transformer Oil Types for Optimal Performance and Sustainability

Conclusion

The decision between the inhibited and uninhibited transformer oil is a strategic, not purely technical choice, as there must be a balance between performance and cost with maintenance considerations. Inhibited oils assure excellent stability and durability under very high stress and voltage applications, while uninhibited oils serve as an economic choice for less demanding applications.

To maximize transformer performance and reduce maintenance costs, rely on INVEXOIL’s Transformer Oil Purification Machine and Transformer Oil Regeneration Services for advanced, tailored solutions.

 

References:

IEC 60296: Fluids for Electrotechnical Applications- Unused Mineral Insulating Oils for Transformers and Switchgear.

IEC 60422: Supervision and Maintenance Guide for Mineral Insulating Oils in Electrical Equipment.

Technical white papers on oxidation inhibitors and transformer oil degradation.

Academic studies comparing the performance of inhibited and uninhibited transformer oils under varying operational conditions.

 

Emad Ghadiri

2 thoughts on “Inhibited and Uninhibited Transformer Oils: What’s the Difference?”